Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Manual Type |
Still deciding? Get samples of US$ 12.66/Piece
Request Sample
|
Suppliers with verified business licenses
Rated current In (A) | 1P+N: 20/25/32/40/50/63/80A 3P+N: 20/25/32/40/50/63/80/100A |
Overvoltage action setting value (L-N) | AC275 ± 5V |
Rated working voltage Ue (V) | 1P+N : 230 AC 3P+N : 400 AC |
Overvoltage recovery value (L-N) | ≤ 253V |
Voltage frequency | 50Hz | Undervoltage tripping time | 0.6-5s |
Conforming to standard | JB/T 12762-2015 | Undervoltage recovery value (L-N) | ≥ 195V |
Overvoltage action setting value (L-N) | AC275 ± 5V | Self reset delay | 25 ± 5s |
Overvoltage tripping time (L-N) | 3~15s(275V); 1-3s(300V) 0.25-0.75s(350V); 0.1~0.2s(400V |
Rated limiting short-circuit current capacity | 20-80A: 6kA 100A: 4.5kA |
Impulse withstand voltage Uimp | 4kV | Electrical life | 10000 times |
Single phase maximum protection voltage | 450V | Protection level | Body: IP20 Installed in the distribution box: IP40 |
Wiring method | Up In Down Out (DZ47sGQF) Down in up out (DZ47sGQR) |
Wiring capability | 1P+N: 25mm² and below 3P+N: 35mm² and below |
Rated torque | 1P+N: 2.5N. m 3P+N: 3.5N. m |
Pollution level | II |
Product name | Number of poles | Rated current |
DZ47sGQF/GQR | 6 | |
DZ47sGQF: top inlet DZ47sGQR: bottom inlet |
Default: 1P+N 6: 3P+N |
20: 20A 25: 25A 32: 32A 40: 40A 50: 50A 63: 63A 80: 80A 100: 100A |